NFPA 80 (Standard for Fire Doors and Other Opening Protectives) governs the installation, inspection, and maintenance of fire-rated door assemblies. For hinges, NFPA 80 specifies material (steel only), minimum leaf thickness, number of hinges per door height, and mandatory self-closing devices. All fire doors must be self-closing and self-latching, with hinges meeting ANSI/BHMA A156.17 Grade 1 for self-closing applications.
| Standard | NFPA 80 (Standard for Fire Doors and Other Opening Protectives) |
|---|---|
| Scope | All fire-rated swinging door assemblies |
| Hinge Material | Steel or stainless steel only (no brass or aluminum on fire doors) |
| Min Hinges | 1 per 30″ (762 mm) of door height, minimum 2 |
| Leaf Thickness | Standard weight 0.134″ up to 4′ wide; Heavy weight 0.180″ over 4′ wide or 8′ tall |
| Self-Closing | Mandatory — listed door closer OR Grade 1 self-closing hinges |
| Self-Latching | Mandatory — door must latch without manual operation |
| Inspection | Annual per NFPA 80 Chapter 5 |
| Last Updated | 2026-02-27 |
Fire-rated doors are a critical element of a building’s passive fire protection system. Unlike standard doors, fire-rated assemblies must remain closed and latched during a fire event to contain smoke and flames and allow safe egress. NFPA 80 establishes the minimum requirements to ensure that every component of a fire door assembly — including the hinges — performs reliably under fire conditions.
The key hinge-related requirements under NFPA 80 address four areas:
Non-compliance with NFPA 80 hinge requirements can result in failed annual inspections, insurance coverage issues, and most critically, reduced fire protection for building occupants.
NFPA 80 restricts hinge materials on fire-rated doors to steel or stainless steel only. Brass, bronze, and aluminum hinges are not permitted because they may weaken or fail at elevated temperatures reached during a fire. This requirement applies regardless of the aesthetic finish — a steel hinge with a brass-colored coating is acceptable, but a solid brass hinge is not.
Hinge leaf thickness requirements are specified in NFPA 80 Table 6.4.3.1 and depend on door width and height. Heavier doors create greater stress on hinges, requiring thicker hinge leaves to maintain structural integrity:
| Door Condition | Hinge Size (Height) | Leaf Thickness (Weight Class) |
|---|---|---|
| Up to 3′ (36″) wide | 4‑1/2″ | 0.134″ (Standard Weight) |
| Up to 4′ (48″) wide | 4‑1/2″ | 0.134″ (Standard Weight) |
| Over 4′ (48″) wide | 4‑1/2″ | 0.180″ (Heavy Weight) |
| Over 8′ (96″) tall | 4‑1/2″ or larger | 0.180″ (Heavy Weight) |
Heavy-weight hinges with 0.180″ leaf thickness are required for oversized doors because the increased mass and leverage place significantly greater stress on each hinge. Using standard-weight hinges on a wide or tall fire door risks hinge deformation over time, which could prevent the door from closing and latching properly.
NFPA 80 requires one hinge for each 30 inches (762 mm) of door height, or fraction thereof, with a minimum of two hinges per door. This formula ensures that hinge loading is distributed adequately across the full door height, preventing warping or binding that could interfere with the door’s self-closing function.
| Door Height | Calculation | Minimum Hinges Required |
|---|---|---|
| 6′8″ (80″) | 80 ÷ 30 = 2.67 → round up | 3 hinges |
| 7′0″ (84″) | 84 ÷ 30 = 2.80 → round up | 3 hinges |
| 8′0″ (96″) | 96 ÷ 30 = 3.20 → round up | 4 hinges |
| 10′0″ (120″) | 120 ÷ 30 = 4.00 | 4 hinges |
Hinge placement should follow standard door hardware placement practices: the top hinge is typically set 5″ from the top of the door, the bottom hinge 10″ from the bottom, and intermediate hinges evenly spaced between them. Exact placement may also be governed by the door manufacturer’s listing requirements — always consult the labeled assembly documentation.
NFPA 80 Section 4.8.3 mandates that all fire-rated swinging doors be equipped with an approved self-closing device. The self-closing requirement exists because an open fire door provides no protection — the door must return to the closed and latched position automatically to function as a fire barrier.
NFPA 80 accepts two primary self-closing solutions for swinging doors:
When self-closing hinges are used as the sole self-closing device (without a separate door closer), NFPA 80 requires a minimum of two spring or self-closing hinges per door. This redundancy ensures that if one hinge mechanism weakens, the remaining hinge can still close the door reliably.
Additional self-closing requirements under NFPA 80:
NFPA 80 Section 4.8.4 requires that fire-rated doors be self-latching: the latch must engage the strike automatically when the door closes, without any manual operation by the occupant. A door that closes but does not latch provides negligible fire protection, as positive latching holds the door firmly in the frame and prevents it from being pushed open by pressure differentials caused by the fire.
Key self-latching requirements:
NFPA 80 Chapter 5 requires that fire door assemblies be inspected and tested annually by a qualified person. The inspection must be documented with the date, name of the inspector, and any deficiencies found and corrected. The following checklist covers hinge-related inspection points:
Deficiencies identified during inspection must be corrected immediately. A fire door that fails inspection must be taken out of service or repaired before it can be relied upon as part of the building’s fire protection system.
When specifying fire door hardware, designers and specifiers can choose from several self-closing approaches, each with distinct trade-offs:
| Self-Closing Option | Pros | Cons |
|---|---|---|
| Self-Closing Hinges (spring type) | Invisible — no surface hardware; no arm or track; less maintenance; lower cost; easy retrofit | Less precise closing speed control; spring tension may decrease over time; slamming possible if not adjusted |
| Hydraulic Closer Hinges | Invisible & adjustable closing speed; meets ADA closing speed requirements; quiet and controlled close | Higher unit cost than spring hinges; requires ANSI/BHMA A156.17 Grade 1 listing |
| Surface Door Closers | Most adjustable (speed, backcheck, delayed action); widest door size range; most familiar to inspectors | Visible hardware on door face; requires mounting arm and track; more maintenance points; can be vandalized |
| Concealed Overhead Closers | Hidden in door and frame; clean aesthetic; no exposed arm | Requires routing of door or frame; harder to adjust and service; higher installation cost |
NFPA 80 requires hinges on fire-rated doors to be made of steel or stainless steel only. The hinges must also meet the minimum leaf thickness requirements (0.134″ standard weight for doors up to 4′ wide; 0.180″ heavy weight for doors over 4′ wide or over 8′ tall). Brass, bronze, and aluminum hinges are not permitted.
NFPA 80 requires one hinge per 30 inches (762 mm) of door height, with a minimum of two hinges. A standard 6′8″ (80″) door requires 3 hinges; an 8′0″ (96″) door requires 4 hinges. Always round up when the calculation yields a fraction.
Yes. Listed ANSI/BHMA A156.17 Grade 1 spring hinges are an acceptable self-closing device under NFPA 80. When spring hinges serve as the sole self-closing mechanism (without a separate door closer), a minimum of two spring hinges must be installed per door. The hinges must be UL-listed or carry equivalent third-party certification for use on fire-rated assemblies.
No. NFPA 80 explicitly restricts hinge material on fire-rated doors to steel or stainless steel. Brass, bronze, and aluminum weaken or melt at temperatures reached in a fire event, which could cause hinge failure and allow the door to open. A steel hinge with a decorative brass finish (brass-plated or brass-toned coating over steel) is acceptable, but a solid brass hinge body is not.
NFPA 80 Chapter 5 requires fire door assemblies to be inspected and tested at least annually. Inspections must be performed by a qualified person and documented with the inspection date, inspector name, and any deficiencies noted and corrected. Some AHJs may require more frequent inspections for high-use locations such as hospital corridors or stairwell doors.
If hinges fail the annual NFPA 80 inspection, the deficiency must be corrected immediately. The inspector must document the deficiency and its correction. In the interim, if the fire door assembly cannot function as intended (e.g., it will not close and latch), the building owner may need to implement temporary compensating measures and notify the AHJ. Repeated or unresolved failures can result in code violations, increased insurance premiums, and liability exposure in the event of a fire.
UL-listed, Grade 1 certified, steel & stainless steel options